Pilots
 
 
  
    
	There is an Eclipse Gas Pilot (Bulletin 810) available for use with virtually 
	any type of industrial burner. Complete pilot assemblies are available in 
	atmospheric types for either low (4" w.c. to 3 psig) or high (3 psig and above) 
	pressure gas. Ignition methods are either manual or electric.
  
Eclipse extended pilots (Bulletin 814) are long, internally spark ignited pilot 
burners. These pilots are primarily used to ignite gas, or combination gas/oil 
burners that are located too far inside the combustion chamber to be reached by 
conventional pilots.
  
Eclipse Nozzle Mixing Pilots (Bulletin 816) are designed to reliable ignite all 
types of gas, oil, or combination gas/oil burners. The 3.5 Series NMP-S pilots 
will ignite burners with inputs to 3,000,000 Btu/hr., and the 51.5 Series pilots, 
depending on the outlet size selected, will ignite burners rated to 20,000,000 Btu/hr.
  
Nozzle mixing pilots are available in two main body sizes. The 3.5 Series NMP-S 
pilots have a 1/2" air inlet and 1/4" gas inlet. They can be ordered with a 3/8", 
1/2", or 3/4" threaded outlet. Maximum capacity of all 3.5 Series NMP-S pilots is 
25,000 Btu/hr. The 51.5 Series NMP-S pilots have a 1-1/4" air inlet and 1/2" gas 
inlet. If ordered with a 3/4" threaded outlet, the 51.5 NMP-S pilot has a maximum 
capacity of 65,000 Btu/hr. With a 1" threaded outlet the 51.5 pilot capacity is 
90,000 Btu/hr. while a 1-1/4" threaded outlet provides 150,000 Btu/hr.
  
Maximum gas inlet pressure for all sizes is 1/2 psig.
	
 
  |  
   
  
 
   